Solis S6-EH3P10K-H-AU 10kW Three Phase High Voltage Hybrid Inverter
Solis S6-EH3P10K-H-AU 10kW Three Phase High Voltage Hybrid Inverter
Please sign in to see pricing

Description
Overview
The Solis S6-EH3P10K-H-AU is a 10kW three-phase high voltage hybrid inverter from the Solis S6-EH3P(5-10)K-H-AU series, designed for solar and battery storage systems on three-phase supplies. The series covers 5kW to 10kW models.
Four MPPTs accept a PV array of up to 20kW (200% of rated output), and the 120–600V battery port charges and discharges at up to 10kW / 50A. A separate backup port supplies 10kW continuously and supports unbalanced three-phase loads.
Key Features
High PV Input Capability
- Four MPPTs, 16A input current and 24A maximum short-circuit current per MPPT
- Up to 20kW recommended PV array size with a 1000V maximum DC input
- Wide 200–850V MPPT operating range
Battery & Backup
- High voltage lithium battery input, 120–600V, with CAN/RS485 BMS communication
- 10kW / 50A maximum charge and discharge
- 10kW backup output, 16kVA for 60 seconds, switch time under 10ms
- Unbalanced three-phase output up to 50% of rated power per phase (single system)
Efficient & Robust
- 97.9% maximum efficiency, 97.51% EU efficiency, up to 98.31% PV-to-battery charging
- Transformerless, IP66 enclosure with natural cooling for -25 to +60°C operation up to 4000m
- Night self-consumption under 25W
- 30.2kg, 600 x 500 x 230mm housing
Monitoring & Control
- LED indicators with Bluetooth app setup
- CAN and RS485, with optional Wi-Fi, cellular or LAN communication
Specifications
| Model | S6-EH3P10K-H-AU |
|---|---|
| Type | Three Phase Hybrid Energy Storage Inverter |
| Topology | Transformerless |
| AC phases | Three |
| Maximum PV array power | 20 kW |
| Maximum PV input voltage | 1000 V |
| Nominal PV input voltage | 600 V |
| MPPT voltage range | 200 – 850 V |
| PV start-up voltage | 160 V |
| Maximum PV input current per MPPT | 4 × 16 A |
| Maximum PV short-circuit current per MPPT | 4 × 24 A |
| Number of MPPTs | 4 |
| Number of PV string inputs | 4 |
| PV connection | MC4 connector |
| Battery operating voltage range | 120 – 600 V |
| Maximum continuous charge current | 50 A |
| Maximum continuous discharge current | 50 A |
| Maximum charge power | 10 kW |
| Maximum discharge power | 10 kW |
| Battery connection | Quick connection plug |
| Supported battery types | Li-ion |
| AC input voltage range | 304 – 437 V |
| Maximum AC input current | 22.7 A / 21.7 A |
| Transfer (switch-over) time | < 10 ms |
| Nominal AC output power | 10 kW |
| Maximum AC apparent power | 10 kVA |
| Nominal backup power (whole-home) | 10 kW |
| Nominal AC output voltage | 380 V / 400 V |
| Nominal AC output frequency | 50 Hz |
| AC input frequency range | 45 – 55 Hz |
| Nominal AC output current | 15.2 A / 14.4 A |
| Maximum AC output current | 15.2 A / 14.4 A |
| Power factor (adjustable range) | > 0.99 (0.8 leading - 0.8 lagging) |
| Total harmonic distortion (THD) | < 3 % |
| Peak backup apparent power | 16 kVA, 60 s |
| Maximum power per phase (unbalanced) | 50% of rated power (single system) |
| Maximum efficiency | 97.90 % |
| European (weighted) efficiency | 97.51 % |
| Standby / night consumption | < 25 W |
| Maximum battery charge efficiency | 98.31 % |
| Maximum battery discharge efficiency | 97.50 % |
| Anti-islanding protection | Yes |
| Reverse polarity protection | Yes |
| Short-circuit protection | Yes |
| AC output over-current protection | Yes |
| Integrated DC switch | Yes |
| Arc-fault protection (AFCI) | Optional |
| PV overvoltage protection | Yes |
| Battery reverse protection | Yes |
| Communication interfaces | CAN / RS485 / Wi-Fi (optional) / Cellular (optional) / LAN (optional) |
| Bluetooth | Yes |
| Wi-Fi | Optional |
| Cellular (4G/LTE) | Optional |
| Display | LED indicator & Bluetooth + APP |
| Operating temperature | -25 – 60 °C |
| Maximum relative humidity | 95 % |
| Maximum altitude | 4000 m |
| Protection rating (IP) | IP66 |
| Noise level | < 46.9 dB(A) |
| Dimensions (W × H × D) | 600 × 500 × 230 mm |
| Weight | 30.2 kg |
| Cooling | Natural cooling |
| AC connection | Quick connection plug |
| Safety standards | IEC/EN 62109-1/-2 |
| EMC standards | IEC/EN 61000-6-1/-3 |
| Grid-connection standards | AS 4777.2:2020 |